Methods & sources

How the checker gets its numbers

Each result tells you what it uses, what can be checked with it, and what still needs a product manual or local review.

Cooktop width → estimateHVI rule of thumb by mounting position.
Airflow and diameter → FPMAverage velocity at the stated airflow.
Documented capacity and appliances → code screenBase IRC condition check, with unknowns preserved.
The HVI estimate can be used for a duct scenario. It does not establish an exhaust system's capability for code review.

Starting airflow

Convert width to feet, then multiply by 100 CFM per foot for a wall location or 150 CFM per foot for an island. These are HVI recommendations, with separate lower values in the guide. For professional-style cooktops, HVI directs buyers to the cooktop manufacturer. The tool has no generic gas BTU modifier. HVI kitchen ventilation guidance

Round duct velocity and length

Area in ft² = π × (inside diameter in inches ÷ 24)². Average speed in FPM = assumed CFM ÷ area in ft². Use the entered capacity when available, otherwise use the HVI starting point as a scenario. The screen searches the listed 4, 5, 6, 7, 8, 10 and 12-inch diameters for the first result at or below 1,800 FPM, comparing before rounding for display. That line is an editorial screening assumption and is not a code limit or a noise test.

The manual worksheet adds measured straight length to the sum of fitting allowances you supply. It compares with the limit you enter from the same hood manual. The tool does not infer fitting losses, pressure, fan performance or delivered airflow.

Model code condition

When no documented capacity is entered, the rule remains unresolved. At or below 400 CFM, the airflow condition is not met. Above 400 CFM, the result reflects whether a qualifying appliance is reported present, absent or unknown. The check is for a U.S. ducted residential kitchen hood and uses the base IRC. Local amendments and accepted evidence can change how a particular installation is reviewed.

Code sources and local variation

International Code Council, 2024 International Residential Code, Chapter 15, §§ M1503.3–.4 and M1503.6–.6.2. ICC Digital Codes may restrict direct access. The two-condition calculation above summarizes the base model section.

The South Carolina Building Codes Council's comparison document shows the 2024 model wording alongside state-specific modification language using the exhaust rate above 400 CFM. Check your own jurisdiction's adopted text and effective date. Council comparison document (PDF)

Illustration notes

Code and HVI references were checked on November 19, 2026. The model comparison cites the manufacturer's document next to each rating, with the configuration stated. The site diagrams show the geometry or decision logic; the homepage AI-generated kitchen illustration provides context for canopy coverage.

Try the checker