Compare round ducts at the same airflow
These figures assume steady airflow through a clear round duct of the stated inside diameter. The checker uses 1,800 FPM as an illustrative comparison line. A row below that line does not establish a quiet or permitted installation.
| Assumed airflow | Velocity in 6 in | First listed size ≤1,800 FPM |
|---|---|---|
| 250 CFM | 1,273 FPM | 6 in · 1,273 FPM |
| 390 CFM | 1,986 FPM | 7 in · 1,459 FPM |
| 400 CFM | 2,037 FPM | 7 in · 1,497 FPM |
| 600 CFM | 3,056 FPM | 8 in · 1,719 FPM |
| 900 CFM | 4,584 FPM | 10 in · 1,650 FPM |
| 1,200 CFM | 6,112 FPM | 12 in · 1,528 FPM |
| 2,500 CFM | 12,732 FPM | None in the 4–12 in list |
Rectangular duct and fittings
A 3¼ × 10-inch rectangular duct has 32.5 in² of geometric area, compared with 28.3 in² for a 6-inch round duct. Equal area only means equal average velocity at equal airflow. Shape, fitting geometry and surface affect pressure loss. Use the hood manual to see whether it permits the specific rectangle or transition.
Use the manual's length method
- Record the collar size, duct shape and material. Measure the straight portions and list each elbow, reducer and terminal cap.
- Find the manufacturer's allowance for each fitting in the relevant configuration. Include the cap if the manual counts it. Where it gives only a layout or fitting-count limit, follow that instruction instead of inventing a length.
- Compare the sum with the manual's maximum for the same configuration. In a hypothetical manual with a 45 ft maximum and 20 ft total fitting allowance, 18 ft of straight duct gives 38 ft. That is within the entered length limit. You still need to verify every fitting and the specified duct material.
The 2024 model IRC addresses smooth interior, outdoor discharge and backdraft dampers in M1503.3, with duct materials in M1503.4. Those rules have defined exceptions. Confirm the adopted edition and applicable instructions before changing the route. Code sources