The 400 CFM make-up air rule

A range hood exhausting outdoors removes air from the home. Check both the hood's exhaust capability and the combustion equipment inside the home's air barrier before applying IRC M1503.6.

What the model rule checks

1. Documented capabilityCan the exhaust system move more than 400 CFM?
2. Appliance conditionIs a qualifying fuel-burning appliance inside the dwelling's air barrier?
If both applyModel IRC calls for make-up air at approximately the exhaust rate.
Decision diagram for a ducted kitchen hood. Confirm missing inputs before using the two-condition result.

Exactly 400 CFM does not exceed the threshold. A 600 CFM hood used at a low speed can still be capable of more than 400 CFM. Have your authority having jurisdiction (usually the local building department) confirm its adopted edition, amendments and what it accepts as evidence of the system's capability. Code sources and local example.

Which appliances count?

The appliance condition concerns gas, liquid or solid fuel equipment within the dwelling unit's air barrier that is neither direct vent nor mechanically draft-vented. An atmospheric water heater with a draft hood inside that boundary is an example to flag. A sealed direct-vent unit by itself does not establish that condition. Check for other appliances, including a fireplace or boiler.

When the venting arrangement is unclear, record the model number and ask your installer to verify it. Efficiency percentages, fuel type and the number of visible vent pipes can be insufficient to classify a particular installation. The air barrier is the boundary limiting air movement between conditioned space and outdoors or adjacent spaces, so a garage or utility room should be checked rather than assumed to be inside.

Why it matters

Exhaust can lower indoor pressure. Under some conditions, a natural-draft vent can spill combustion gases indoors. The result depends on the building, the appliance, other exhaust equipment and how air enters. The checker does not estimate pressure or assess combustion safety.

What to ask an installer

  • What is the design exhaust rate for this installation, and what outdoor air supply would match it?
  • Will outdoor air enter passively or through a powered system? How will the damper operate with the hood under the locally adopted rule?
  • Where will the supply air enter, how will it reach the kitchen, and how will performance and appliance venting be checked after installation?

Model IRC M1503.6.1 and M1503.6.2 cover delivery location and damper details. Existing building ventilation or an open window should not be assumed to satisfy those provisions. Space-cooling exhaust has a separate exception that is outside this kitchen-hood checker.