Trace the incoming air path
Model IRC M1503.6.1 addresses delivery in the exhaust room or through permanent openings connecting it with another room or duct system. Ask about drafts and how the proposed outlet interacts with the hood's capture zone. For a central air-handler connection, have the installer check the equipment manual, approved outdoor air conditions and control sequence. Code sources and local variation
Size from performance data
Ask for the target delivered supply airflow, the design pressure, and the rated performance of the intake, damper and any fan at that condition. A passive damper opens an air path; its opening diameter alone does not tell you how much air passes. A powered system also needs a performance check through the actual route. Broan damper size and configuration examples (PDF)
Do not use the exhaust duct velocity comparison as a supply-system sizing table. The design airflow, restrictions and available pressure must all be checked for the supply side.
Estimate the winter sensible load
For an illustrative supply of 600 CFM warming from 10°F to 68°F, the sensible heat rate is about 37,600 Btu/h (1.08 × 600 × 58), using 60 min/h, air density 0.075 lb/ft³ and specific heat 0.24 Btu/(lb·°F). This is a load estimate for that airflow and temperature rise, before equipment selection. It excludes humidity effects, altitude adjustment, distribution losses and runtime or utility costs.
Compare what each quote includes
| Line item | Ask the contractor to specify |
|---|---|
| Supply equipment | Intake, damper, any fan or tempering equipment, and performance at the proposed design point. |
| Installation | Duct route, openings and repair, controls, electrical work, applicable permit fees, and exclusions. |
| Verification | Airflow, interlock operation and any required testing or balancing. Request the results in writing. |
Get local itemized prices tied to the same route and documented airflow. Ask separately about the exhaust hood and duct if they are in the same quote.
Questions to take to the estimate visit
- Which locally adopted requirement and airflow basis is the quote using?
- How will the hood start or open the supply system at the relevant speeds?
- What will the installer measure after installation, and who handles the permit or inspection?